800KW柴油发电机组英文资料详情Generating set 1000 KVA

Diesel engine :

  1. Diesel four stroke
  2. Suitable for the power of generating set
  3. RPM : 1500
  4. Cooling : water cooled by fan and radiator
  5. Greasing : by oil through automatic special pump + circuit for heating the water and oil
  6. Starting : electrically starting
  7. Db : Please offer the DB
Starting instruments :
1.      Starter
2.      Battery charger with regulator
3.      Set of batteries ,in meta box with measuring apparatus
4.      and all necessary for working
Diesel measuring apparatus :
1.      RPM
2.      Oil pressure
3.      Oil Temperature
4.      Water Temperature
5.      Hour counter
Diesel accessories :
  1. Pump and filter for fuel with all connection and accessories
  2. Pump and filter for oil
  3. Oil radiator separately
  4. Guide of oil level
  5. Manual pump for new oil
  6. Filter oily for inlet air
  7. Exhaust system with silencer ,expansion joint from stainless steel
Alternator :
  1. 3 phases self excited ,brushless , self regulation , self cooling 1000 KVA
  2. With neutral
  3. Voltage : 220/380 V , Cos phi not less than 0.80
  4. Frequency : 50HZ +/- 1
  5. Equipped with automatic voltage regulator between 0- 100%load
 
Electric switchboard :
  1. Digital Voltmeter + comm..
  2. Digital 3 Ampermeters + current transformers
  3. Digital Hz meter
  4. Digital COS phi
  5. Digital hour counter
  6. Selector (man. / auto)
  7. Starting system : 3 attempt , if not succeed alarm audiovisual
  8. Indicating lamps ( able to change )    (city net , set ,fault starting , over load , low oil pressure , high engine temperature , low fuel level , engine fault , high  oil temperature , fault in alternator , over speed )
  9. Push-buttons for ( start , emergency stop ,restarting , close lamp of engine fault , close the alarm ,)
  10. Audiovisual alarm : feeding from city net
  11. Audiovisual alarm : cut of city net
  12. Push-button for stop the sound alarm
  13. All protection for the alarm system fuses at front of switchboard
  14. Metallic stickers for all functions
  15. electric diagram
  16. the buss bars should be current density < 2 A /mm2
  17. the switchboard should be IP 55
  18. Switchboard door with suitable Key
  19. Switchboard should be earthed
  20. 3 copies from catalogues in English language
  21. Measurements : Digital ( RPM , Oil temperature , water temperature ) water pressure , low oil pressure
  22. Charger : electric charger with all signals for finishing the charging with battery voltage meter .
 
Protection system :
1.      Manual starting
2.      Manual stop (engine , Switchboard)
3.      Over load (sound alarm +light signal +engine shut down ) 
4.      Reverse power (sound alarm +light signal +engine shut down ) 
5.      Over speed(sound alarm +light signal +engine shut down ) 
6.      Low oil pressure (sound alarm +light signal +engine shut down ) 
7.      High temperature (sound alarm +light signal +engine shut down ) 
8.      water over pressure (sound alarm +light signal +engine shut down ) 
9.      should be indicating lamp when the engine work
10.oil pressure (sound alarm +light signal   ) 
11.control the protection circuit ( light signal   )
12.Stop the alarm
13.Reset
14.Over voltage (sound alarm +light signal +engine shut down ) 
15.Short circuit (sound alarm +light signal +engine shut down ) 
16.Phase failure ,or change phases and starting the generating set (sound alarm +light signal   )
17.Set of maintenance tools for montage and erection
Spare parts:

Detailed table of priced spare parts for two years operation  