Diesel engine :
- Diesel four stroke
- Suitable for the power of generating set
- RPM : 1500
- Cooling : water cooled by fan and radiator
- Greasing : by oil through automatic special pump + circuit for heating the water and oil
- Starting : electrically starting
- Db : Please offer the DB
Starting instruments :
1. Starter
2. Battery charger with regulator
3. Set of batteries ,in meta box with measuring apparatus
4. and all necessary for working
Diesel measuring apparatus :
1. RPM
2. Oil pressure
3. Oil Temperature
4. Water Temperature
5. Hour counter
Diesel accessories :
- Pump and filter for fuel with all connection and accessories
- Pump and filter for oil
- Oil radiator separately
- Guide of oil level
- Manual pump for new oil
- Filter oily for inlet air
- Exhaust system with silencer ,expansion joint from stainless steel
Alternator :
- 3 phases self excited ,brushless , self regulation , self cooling 1000 KVA
- With neutral
- Voltage : 220/380 V , Cos phi not less than 0.80
- Frequency : 50HZ +/- 1
- Equipped with automatic voltage regulator between 0- 100%load
Electric switchboard :
- Digital Voltmeter + comm..
- Digital 3 Ampermeters + current transformers
- Digital Hz meter
- Digital COS phi
- Digital hour counter
- Selector (man. / auto)
- Starting system : 3 attempt , if not succeed alarm audiovisual
- Indicating lamps ( able to change ) (city net , set ,fault starting , over load , low oil pressure , high engine temperature , low fuel level , engine fault , high oil temperature , fault in alternator , over speed )
- Push-buttons for ( start , emergency stop ,restarting , close lamp of engine fault , close the alarm ,)
- Audiovisual alarm : feeding from city net
- Audiovisual alarm : cut of city net
- Push-button for stop the sound alarm
- All protection for the alarm system fuses at front of switchboard
- Metallic stickers for all functions
- electric diagram
- the buss bars should be current density < 2 A /mm2
- the switchboard should be IP 55
- Switchboard door with suitable Key
- Switchboard should be earthed
- 3 copies from catalogues in English language
- Measurements : Digital ( RPM , Oil temperature , water temperature ) water pressure , low oil pressure
- Charger : electric charger with all signals for finishing the charging with battery voltage meter .
Protection system :
1. Manual starting
2. Manual stop (engine , Switchboard)
3. Over load (sound alarm +light signal +engine shut down )
4. Reverse power (sound alarm +light signal +engine shut down )
5. Over speed(sound alarm +light signal +engine shut down )
6. Low oil pressure (sound alarm +light signal +engine shut down )
7. High temperature (sound alarm +light signal +engine shut down )
8. water over pressure (sound alarm +light signal +engine shut down )
9. should be indicating lamp when the engine work
10.oil pressure (sound alarm +light signal )
11.control the protection circuit ( light signal )
12.Stop the alarm
13.Reset
14.Over voltage (sound alarm +light signal +engine shut down )
15.Short circuit (sound alarm +light signal +engine shut down )
16.Phase failure ,or change phases and starting the generating set (sound alarm +light signal )
17.Set of maintenance tools for montage and erection
Spare parts:
Detailed table of priced spare parts for two years operation